Modbus Query
A guide on how to frame a Modbus query
Modbus query command
[[Modbus query 1],[Modbus query 2],.....]
Things required to make Modbus query
Slave ID
Function code
Starting address
How many registers/coils want to be read
Data type
Index
Modbus query format
[ Slave ID, Function code, Starting address, No. of registers/coils want to read, Data type, Index]
How to choose function code
It depends on starting address of the register or coil.
Coil status
00001 on words
1
Input Coil status
10001 on words
2
Holding register
40001 on words
3
Input holding register
30001 on words
4
How to choose starting address & number of registers
For eg: if we want to read the parameters like
Watts Total
,Watts R phase
,Watts Y phase
,Watts B phase
, andVAR Total
from the ElmeasureEN8400
Energy meter then its address is from 40101 to 40110. so now the starting address would be 100 & no. of registers want to read would be 10.NOTE: The number of register would be 2 in order to read single parameter of data type float, UINT32, INT32 & for rest it would be 1.
How to choose the data type
Supported data types & formats are:
Datatypes case noDatatypeRemark0
Float ABCD
1
Float DCBA
2
Float BADC
3
Float CDAB
Generally, the datatype mentioned in the datasheet will be without data format[A, B, C, D sequence], for example,
datatype is float
. In that case, use this format[default].4
UINT ABCD
5
UNIT DCBA
6
UINT BADC
7
UINT CDAB
Generally, the datatype mentioned in the datasheet will be without data format[A, B, C, D sequence], for example,
datatype is UINT32
. In that case, use this format[default].8
INT ABCD
9
INT DCBA
10
INT BADC
11
INT CDAB
Generally, the datatype mentioned in the datasheet will be without data format[A, B, C, D sequence], for example,
datatype is INT32
. In that case, use this format[default].12
INT AB
Generally, the datatype mentioned in the datasheet will be without data format[A, B sequence], for example,
datatype is INT16
. In that case, use this format[default].13
INT BA
14
UINT AB
Generally, the datatype mentioned in the datasheet will be without data format[A, B sequence], for example,
datatype is UINT16
. In that case, use this format[default].15
UINT BA
In case of Coil status or input Coil status data type is not mandatory, we can choose default data type 0.
Note: In some exceptional cases even after selecting the [default] data format, we will observe that we are not receiving data from the slave in that scenario we have to do a trial & error by selecting a different data format until we will receive the data
.
Index
Index number is nothing but a number of queries you have? The first query index is 0.
Example Queries
Schneider meter EM6436
UART: {"action":"modbus", "mb_mode":"1", "baud":"4800", "data_bits":"8", "parity":"EVEN", "stop_bits":"1", "mb_interval":"2000", "mb_timeout":"1000"}
[[1,3,3000,20,3,0], [1,3,3030,20,3,1], [1,3,3060,20,3,2], [1,3,3090,20,3,3], [1,3,3120,4,3,4], [1,3,3150,4,3,5]]